HPM2.Z

HPM2.Z - an integrated set consisting of the external unit HPMO2 and the internal unit HPMI2 for installation in new and modernized systems.

The HPM2.Z system includes:

  • external unit HPMO2
  • internal unit type HPMI2
Kospel
Description

Internal Unit HPMI2

Heating unit with weather control, equipped with a hydraulic group and an electric heating set

  • quick installation, thanks to matched elements placed in a compact housing
  • advanced control capabilities:
    • weather control heating
    • daily and weekly temperature regulation cycle in the room and domestic hot water
    • control of 2 heating circuits + domestic hot water circuit
  • electric heating set with automatic power modulation:
    • **3/6 kW for HPMO2-8 and HPMO2-12
    • ***3/6/9 kW for HPMO2-16/23
  • hydraulic group:
    • three-way dividing valve, which allows water heating in cooperation with the domestic hot water exchanger
    • safety group - diaphragm vessel with a capacity of 12 l, safety valve, electronic pressure gauge, automatic air vent
  • remote control via the internet using the C.MI2 module (additional equipment)

External Unit HPM2

The pump installation is easier thanks to the built-in hydraulic group. The devices included in it are essential for the correct operation of the installation. The hydraulic group contains:

  • Energy class: A+++(35 °C)/A++ (55 °C) 
  • Refrigerant R32
  • EVI injection system ensures high efficiency and water temperature up to 60°C
  • Wide operating range at external air temperature from -25°C to +43°C 
  • Quiet device operation – sound pressure level at a distance of 1m: 52 to 56 dB(A)  depending on the selected device power - Q2 coefficient 
  • Planar room cooling or cooperation with a fan coil + Frost protection 
  • Smooth power modulation ensures optimal operation depending on heating needs from 2.3 to 8.2kW (A7/W35) 

Watch the video and learn about the KOSPEL heat pump heating system

Sets
HPM2.Z-8HPM2.Z-12HPM2.Z-16
The heat pump system includes:
  • external unit HPMO2-8
  • internal unit HPMI2
The heat pump system includes:
  • external unit HPMO2-12
  • internal unit HPMI2
The heat pump system includes:
  • external unit HPMO2-16
  • internal unit HPMI2
Technical data
Product CodeHPM2.Z-8HPM2.Z-12HPM2.Z-16
Energy Efficiency Class A+++ (35 °C) / A++ (55 °C) A+++ (35 °C) / A++ (55 °C) A+++ (35 °C) / A++ (55 °C)
Maximum Heating Power of the Heat Pump (kW) 5.8 (A-7/W35)
7.1 (A+2/W35)
8.2 (A+7/W35)
9.2 (A-7/W35)
11.3 (A+2/W35)
12.5 (A+7/W35)
17.1 (A-7/W35)
20.5 (A+2/W35)
23.0 (A+7/W35)
Efficiency Coefficient COP up to: 4.6 (A+7/W35)
4.01 (A+2/W35)
3.49 (A-7/W35)
4.75 (A+7/W35)
3.94 (A+2/W35)
3.37 (A-7/W35)
4.76 (A+7/W35)
4.02 (A+2/W35)
3.47 (A-7/W35)
Sound Power Level dB (A) 60 63 64
Max Sound Pressure Level dB(A) - Coeff. Q2 52 55 56
Power Supply 400 V 3N~ / 230 V~ 400 V 3N~ / 230 V~ 400 V 3N~~
Max Coolant Temperature 60oC 60oC 60oC
Nominal Current of the Overcurrent Circuit Breaker 3x16A / 40A 3 x 25 A / 50 A 3 x 32A
Min. Cross-Section of the Supply Cable 5 x 2.5 mm2 / 3x6 mm2 5 x 2.5 mm2 / 3x6 mm2 5 x 2.5 mm2